SMS Loop Card

Stock Code: SENTRI2-LPC-EN

The SMS SENTRI2-LPC-EN Loop Card is designed to fully comply with EN54-23 and is available for EN54 versions of the SenTRI TWO and SenTRI FOUR fire alarm systems. Its enhanced power capability supports up to 100 EN54-23 compliant sensor-sounder-strobe devices, with a total capacity of up to 200 devices per loop.

The loop card supports a minimum loop length of 1 km; however, actual loop design limits must be verified using the loop load design calculator. This tool also evaluates the impact of alarm device distribution, as evenly balanced loads using the latest devices may allow for extended loop lengths.

During loop allocation, the card automatically measures and displays loop resistance on the control panel, simplifying the commissioning process. If the measured resistance exceeds safe operating limits, the system will generate a fault indication to alert the engineer.

Key Features:

  • Increased capacity for loop-powered devices, including EN54-23 visual alarm devices

  • Loop current increased to 800 mA when used with the latest SenTRI devices

  • Enhanced efficiency delivering twice the alarm power without reducing standby time

  • Supports up to 100 EN54-23 certified SenTRI Sensor Sounder VADs

  • Enables upgrades to existing SenTRI installations

Related Products

Alternatives

We have placed cookies on your device to help make this website better.

Your Basket
Subtotal
Discount
VAT
Total (inc VAT)
Total (ex VAT)

Your order contains no items